译 者 说数据中心采取先进的消防系统,并实行全面的概括、检测和扼制计策,以平缓潜在的失火危急。尽管采取了这些门径,数据中心失火天然看似荒野,每年在大师数千个门径中只发生几来源要事件,但仍组成了进犯淡薄的首要要挟。
Windstream – 内布拉斯加州林肯数据中心失火Windstream – Lincoln, Nebraska Data Center Fire图片
2023年9月,位于内布拉斯加州林肯市中心M街1440号的Windstream数据中心发生失火,形成价值20万好意思元的亏空。该事件使内布拉斯加州东南部多个县的 911行状在夜间严重中断了几个小时。 In September 2023, a fire broke out at Windstream’s data center located at 1440 M St in downtown Lincoln, Nebraska, resulting in $200,000 worth of damage. The incident severely disrupted 911 services in multiple Southeast Nebraska counties for several hours during the night.失火缘由是电气终止室漏水,激勉渺小爆炸。此次爆炸导致变压器短路,导致室内三处同样开关断电。尽管现场备用发电机少顷规复了电力,但它也发生了故障,导致数据中心依赖于其备用电板。 The fire originated from a water leak in the electrical control room, triggering a minor explosion. This explosion caused a transformer to short-circuit, disabling power to three switches in the building. Although an on-site backup generator briefly restored power, it too malfunctioned, leaving the data center dependent on its battery backup.
图片
面对这些挑战,Windstream的本事团队不得不关闭三处同样开关,影响了内布拉斯加州亚当斯县、盖奇县、奥托县和桑德斯县的911畅达。东南地区的其他县也可能出现行状中断的情况。红运的是,莫得东谈主员受伤的论说。消防队员使用干粉和二氧化碳熄灭器到手扑灭了大火。 Faced with these challenges, Windstream’s technical team had to shut down one of the three switches, affecting 911 connectivity in Nebraska’s Adams, Gage, Otoe, and Saunders Counties. Other counties in the Southeast region might have also experienced service interruptions. Fortunately, there were no reported injuries. Firefighters successfully put out the fire using dry chemicals and CO2 extinguishers.
Proximus – 比利时布鲁塞尔数据中心失火Proximus – Brussels, Belgium Data Center Fire2023年8月,比利时最大无线运营商和固定宽带提供商Proximus运营的Netcenter Evere数据中心发生失火。位于布鲁塞尔东北郊埃弗雷(Evere)卡利街 1140号的该门径遭受了严重碎裂。 In August 2023, a fire erupted at the Netcenter Evere data center, which is operated by Proximus, Belgium’s largest wireless carrier and fixed broadband provider. Located in Evere, a northeastern suburb of Brussels at Rue Carli, 1140, the facility experienced a significant disruption.
图片
消防队员在90分钟内到手终止了火势,使数据中心规复平素运行。然则,该事件导致暂时中断,影响了伏击电话行状。具体来说,伏击电话号码112(消防员和救护车)和101(巡警)在不到30分钟的时刻里齐无法拨打。Proximus当今正在造访中断原因。 Firefighters managed to control the fire within 90 minutes, allowing the data center to resume normal operations. However, the incident led to a temporary outage that affected emergency phone services. Specifically, the emergency numbers 112 – for firefighters and ambulances – and 101 – for police – were unavailable for less than 30 minutes. Proximus is currently investigating the cause of the outage.
Digital Realty – 加利福尼亚州洛杉矶数据中心失火Digital Realty – Los Angeles, California Data Center Fire2023年5月,大师最大的数据中心提供商之一Digital Realty 位于加利福尼亚州埃尔塞贡多东埃尔塞贡多正途2260号的洛杉矶LAX12门径发生首要失火事件。失火发源于一个特定的机架,导致这座占地132,000平方英尺的两层门径内的两套门径关闭,该门径撑合手7.45MW的UPS电力容量。该事件严重扯后腿了数据中心的运营。其中一套门径在数小时内就赢得了竖立,但另一套几天后仍无法使用。
In May 2023, Digital Realty, one of the world’s largest data center providers, experienced a significant fire incident at its Los Angeles LAX12 facility, located at 2260 East El Segundo Boulevard in El Segundo, California. The fire, which originated in a specific rack, prompted a shutdown of two suites within the two-story, 132,000 square foot facility, which supports 7.45 megawatts of UPS power capacity. This incident considerably disrupted the data center’s operations. One suite was restored within hours, however another remained out of commission for several days.
图片
失火触发了主机托管空间的喷水熄灭系统,导致很多行状器遭受水浸。这种挫伤关于Evocative来说尤其严重,Evocative是一家以Krypt品牌运营并合手有前VPLS 和INAP旗下钞票的托管行状提供商。尽管造访仍在进行中,但生气的真确原因仍未笃信。
The fire triggered the sprinkler system in the colocation space, resulting in water damage to many servers. This damage was particularly severe for Evocative, a managed services provider that operates under the brand Krypt and holds assets from the former VPLS and INAP banners. Despite ongoing investigations, the exact cause of the fire remains undetermined.
Global Switch – 法国巴黎数据中心失火Global Switch – Paris, France Data Center Fire2023年4月,欧洲和亚太地区主要数据中心运营商Global Switch位于法国巴黎西北部郊区克利希Rue Petit 7-9号的巴黎东和巴黎西数据中心发生失火。该门径共有六层,总面积为555,612平方英尺(51,618平方米),现存和推测打算总容量为59 MVA,由于电板室生气,该门径履历了4 个半小时的中断。 In April 2023, Global Switch, a major data center operator in Europe and Asia-Pacific, experienced a fire at its Paris East and Paris West data centers located at 7-9 Rue Petit in Clichy, France, a suburb in the northwestern region of Paris. The facility, which consists of six floors with 555,612 square feet (51,618 square meters) of gross space and 59 MVA of current and planned capacity, faced disruption for 4 hours and 30 minutes due to a fire in its battery room.
失火是由冷却系统水泵故障导致漏水激勉的,这与数据中心空调系统的问题筹办。清楚的水浸透电板室,与电板组件战斗后激勉失火。 The fire was triggered by a water leak resulting from a cooling system water pump failure, which was linked to an issue in the data center’s air conditioning system. The water from the leak infiltrated the battery room, instigating a fire upon contact with the battery components.
图片
天然火势被终止在电板室,但该事件导致位于Global Switch巴黎数据中心的 Google Cloud Europe-west-9区域的精深数据丢失。该地区际遇了基础门径故障,影响了多项谷歌云行状,现代激情止境是在europe-west9-a区域。领先,漏水只影响了europe-west9-a的一部分,但随后发生的失火导致整个这个词区域以及europe-west9-c区域的一部分暂时断电。 While the fire was contained to the battery room, the incident resulted in significant data loss for Google Cloud’s europe-west-9 region, which resides in Global Switch’s Paris data centers. This region suffered an infrastructure failure that affected several Google Cloud services, particularly in the europe-west9-a zone. Initially, the water leak had only affected a part of europe-west9-a, but a subsequent fire required the entire zone, along with a portion of the europe-west9-c zone, to be temporarily powered down.
Maxnod – 法国艾因数据中心失火Maxnod – Ain, France Data Center Fire2023年3月,位于法国艾因穆瓦尼昂河滨圣特里维耶,由Adeli运营的Maxnod数据中心发生失火。该门径占地8,611平方英尺(800平方米),遭受了严重损坏,需要澈底重建。数据中心内的开荒也被澈底碎裂。 In March 2023, a fire occurred at the Maxnod Datacenter, operated by Adeli, in Saint-Trivier-sur-Moignans, Ain, France. Spanning 8,611 square feet (800 square meters), the facility sustained significant damage that necessitated a complete reconstruction of the building. The equipment within the data center was also completely destroyed.
图片
缺憾的是,又名消防员在事件中受轻伤。生气原因可回顾到该门径太阳能电板板的电板室,据信是由锂离子电板引起的。失火还对数据中心的光缆形成精深损坏,影响了腹地光纤到户(FTTH)行状。
Regrettably, one firefighter sustained minor injuries during the incident. The cause of the fire was traced back to the battery room of the facility’s solar panels, believed to have been ignited by a lithium-ion battery. The fire also resulted in extensive damage to the data center’s fiber optic cables, impacting local fiber-to-the-home (FTTH) services.
Cyxtera – 马萨诸塞州波士顿数据中心失火Cyxtera – Boston, Massachusetts Data Center Fire2023年2月,零卖托管提供商Cyxtera Technologies位于马萨诸塞州沃尔瑟姆 温特街580号的波士顿BOS1园区发生失火。该数据中心占地40,500平方英尺,领有 16MW的市电电力,但际遇了合手续数小时的中断。 In February 2023, Cyxtera Technologies, a retail colocation provider, experienced a fire at its Boston BOS1 Campus located at 580 Winter Street in Waltham, Massachusetts. The data center, which boasts 16 megawatts of utility power across 40,500 square feet of raised floor space, underwent a disruption that lasted several hours.
事故缘由是数据中心能源室发生弧闪激勉爆炸,炸毁了一个电板柜。爆炸的力量如斯之大,甚至于将电板柜的门炸掉了。随后据报谈数据中心内冒烟,追查到损坏的电气开荒。 The incident originated from an electrical arc flash in the data center’s power room, which caused an explosion that destroyed a battery cabinet. The force of the explosion was such that it blew the doors off the battery cabinet. Smoke was subsequently reported inside the data center, traced back to the damaged electrical equipment.
图片
尽管建筑结构莫得受损,但由此产生的烟雾和爆炸促使当地消防部门出于安全原因强制关闭现场电源,导致大楼内东谈主员疏散。此次断电不测中导致了Cyxtera客户 Oracle NetSuite行状的数据丢失,在规复历程中丢失了约莫30分钟的数据。 Although the building structure remained undamaged, the resulting smoke and explosion prompted the local fire department to enforce a shutdown of power at the site for safety reasons, leading to an evacuation of the building. This power cut inadvertently caused data loss for Oracle’s NetSuite service, a customer of Cyxtera, with approximately 30 minutes of data being lost during the recovery process.
哈瓦贾大厦 – 孟加拉国达卡数据中心失火Khawaja Tower – Dhaka, Bangladesh Data Center Fire2023年10月26日,位于孟加拉国达卡莫哈卡利社区Bir Uttam AK Khandaker 路的哈瓦贾大厦发生首要失火。大火从大楼的12层和13层开动,合手续了15个多小时才被扑灭。该楼高14层,领有由NRB Telecom和 Dhakacolo运营的两个关键数据中心。这些门径至关关键,它们畅达到多个互联网网关和交换机,并为数百家互联网行状提供商 (ISP) 提供行状。
In October 2023, a significant fire broke out in the Khawaja Tower located on Bir Uttam AK Khandaker Road in the Mohakhali neighborhood of Dhaka, Bangladesh. The fire, which lasted for over 15 hours before being extinguished, started on the 12th and 13th floors of the building. The tower, standing 14 stories tall, hosted two major data centers operated by NRB Telecom and Dhakacolo. These facilities were vital, connecting to multiple internet gateways and exchanges and servicing hundreds of internet service providers (ISPs).
图片
失火形成了不同进程的亏空。天然一些开荒被点火,但其他部分基本上毫发无伤。电缆损坏和必要的电力中断导致行状中断。该事件的径直效果是,孟加拉国1210 万宽带用户中约40%用户面对中断。此外,天下1.2亿出动互联网用户中近20%用户的数据和语音行状均出现中断。
The fire inflicted varying degrees of damage. While some equipment was burned, other parts remained mostly unscathed. Damaged cables and a necessary electricity cut-off resulted in service disruptions. As a direct outcome of this incident, approximately 40% of Bangladesh’s 12.1 million broadband users faced outages. Additionally, close to 20% of the nation’s 120 million mobile internet subscribers experienced disruptions in both data and voice services.
缺憾的是,失火不仅挫伤了开荒和行状。它还夺去了3东谈主的生命,并形成至少10 东谈主受伤。官方尚未施展失火的根底原因。然则,尽管有一些熄灭器,但由于存在精深可燃材料,何况建筑物彰着缺少全面的安全主见,情况变得愈加恶化。
Regrettably, the fire wasn’t just detrimental to equipment and services. It claimed three lives and resulted in at least 10 injuries. The root cause of the blaze has not been officially stated. However, the situation was exacerbated by the presence of numerous combustible materials and an apparent lack of a comprehensive safety plan for the building, despite the presence of some fire extinguishers.